SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
635
2 Parameters
2.2 List of parameters
Note: The individual bits are only set if the appropriate action has been initiated and successfully completed.
When motor rating plate parameters are changed, the final display is reset.
Description: Successfully completed component of the last motor data identification carried out.
Dependency: Refer to: r3925
Note: The parameter is a copy of p1909.
08 Identified motor data are automatically
backed up
Yes No -
10 Automatic parameterization only for U/f
control (r0108.2 = 0)
Yes No -
15 Motor equivalent circuit diagram parameters
changed
Yes No -
18 Circle identification executed Yes No -
r3927[0...n] Motor data identification control word / MotID STW
VECTOR_G Can be changed: - Calculated: CALC_MOD_ALL Access level: 3
Data type: Unsigned32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Motor identification Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Stator inductance estimate no
measurement
Yes No -
01 Cl.-loop current control w/ dead-beat
controller
Yes No -
02 Rotor time constant estimate no
measurement
Yes No -
03 Leakage inductance estimate no
measurement
Yes No -
04 Activates the identification dynamic leakage
inductance
Yes No -
05 Determine Tr and Lsig evaluation in the time
range
Yes No -
06 Activate vibration damping Yes No -
07 Deactivate vibration detection Yes No -
11 Deactivate pulse measurement Lq Ld Yes No -
12 Deactivate rotor resistance Rr
measurement
Yes No -
14 Deactivate valve interlocking time
measurement
Yes No -
15 Determine only stator resistance, valve
voltage fault, dead time
Yes No -
16 Short motor identification (lower quality) Yes No -
17 Measurement without control parameter
calculation
Yes No -
18 After motID direct transition into operation Yes No -
19 After MotID automatically save results Yes No -
20 Estimate cable resistance Yes No -
21 Calibrating the output voltage measurement Yes No -
22 Only identify circle Yes No -
23 Deactivate circle identification Yes No -
24 Circle identification with 0 and 90 degrees Yes No -
25 Deactivate gating unit switchover Yes No -