Siemens G130 - p4068[0...1] TB30 analog inputs noise suppression window; TB30 AI window; p4069[0...1] BI: TM31 analog inputs signal source for enable; TM31 AI enable; p4069[0...1] BI: TB30 analog inputs signal source for enable; TB30 AI enable; p4071[0...1] CI: TM31 analog outputs signal source; TM31 AO s_src

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
655
2 Parameters
2.2 List of parameters
Description: Sets the noise suppression window of the analog inputs for Terminal Board 30 (TB30).
Changes less than the window are suppressed.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note: AI: Analog Input
Description: Sets the signal source for the enable signal of the analog inputs of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the signal source for enabling the analog inputs of the Terminal Board 30 (TB30).
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Description: Sets the signal source for the analog outputs of Terminal Module 31 (TM31).
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Note: AO: Analog Output
p4068[0...1] TB30 analog inputs noise suppression window / TB30 AI window
TB30 Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 20.00 [%] 0.00 [%]
p4069[0...1] BI: TM31 analog inputs signal source for enable / TM31 AI enable
TM31 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p4069[0...1] BI: TB30 analog inputs signal source for enable / TB30 AI enable
TB30 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9104
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p4071[0...1] CI: TM31 analog outputs signal source / TM31 AO s_src
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 9549, 9572
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0