2 Parameters
2.2 List of parameters
SINAMICS G130/G150
658 List Manual (LH2), 07/2016, A5E03263479A
Description: Activates the absolute value generation for the analog outputs of the Terminal Board 30 (TB30).
Value: 0: No absolute value generation
1: Absolute value generation switched in
Index: [0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Description: Sets the type of analog outputs of Terminal Module 31 (TM31).
p4076[x] = 1, 4 correspond to a voltage output (p4074, p4078, p4080, p4083 are displayed in V).
p4076[x] = 0, 2, 3 correspond to a current output (p4074, p4078, p4080, p4083 are displayed in mA).
Value: 0: Current output (0 mA ... +20 mA)
1: Voltage output (0 V ... +10 V)
2: Current output (+4 mA ... +20 mA)
3: Current output (-20 mA ... +20 mA)
4: Voltage output (-10 V ... +10 V)
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency: Refer to: p4077, p4078, p4079, p4080
Note: When changing p4076, the parameters of the scaling characteristic (p4077, p4078, p4079, p4080) are overwritten
with the following default values:
For p4076 = 0, 3, p4077 is set to 0.0 %, p4078 to 0.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA.
For p4076 = 1, 4, p4077 is set to 0.0 %, p4078 to 0.0 V, p4079 to 100.0 % and p4080 to 10.0 V.
For p4076 = 2, p4077 is set to 0.0 %, p4078 to 4.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA.
Description: Displays the type of analog outputs of the Terminal Board 30 (TB30).
Value: 4: Voltage output (-10 V ... +10 V)
Index: [0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
p4075[0...1] TB30 analog outputs activate absolute value generation / TB30 AO absVal act
TB30 Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 9106
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p4076[0...1] TM31 analog outputs type / TM31 AO type
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: 9572
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4 4
r4076[0...1] TB30 analog outputs type / TB30 AO type
TB30 Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
4 4 -