2 Parameters
2.2 List of parameters
SINAMICS G130/G150
728 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the scaling for the offset of the signal waveforms separately for each output channel.
The value cannot be changed while the function generator is running.
Index: [0] = First drive for connection
[1] = Second drive for connection
[2] = Third drive for connection
Description: Displays the output signal for the free measurement function.
Index: [0] = Signal 1
[1] = Signal 2
[2] = Signal 3
[3] = Signal 4
[4] = Signal 5
Dependency: Refer to: p4810
Note: The signals are only output in the "free measurement function" operating mode (p4810 = 6)
Description: Sets the scaling of the output signals for the free measurement function.
Index: [0] = Signal 1
[1] = Signal 2
[2] = Signal 3
[3] = Signal 4
[4] = Signal 5
Note: The parameter cannot be changed when the measurement function has been started (r4706 = 2, 3).
Description: Sets the number of cycles of a multiple trace.
The multiple trace is deactivated with a value = 0.
p4833[0...2] Function generator offset scaling / FG offset scal
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
-340.28235E36 [%] 340.28235E36 [%] 100.00000 [%]
r4834[0...4] CO: Function generator free measurement output signal / FG fr MeasFct outp
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 0
Min Max Factory setting
- [%] - [%] - [%]
p4835[0...4] Function generator free measurement function scaling / FG fr MeasFct scal
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
-200.00000 [%] 200.00000 [%] 100.00000 [%]
p4840[0...1] MTrace cycle number setting / Cycle number
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0 4294967295 0