2 Parameters
2.2 List of parameters
Description: Sets the alarm threshold for monitoring the motor temperature for motor temperature models 1 and 3.
The stator winding temperature (r0632) is used to initiate the signal.
The following applies for temperature model 1 (I2t):
- only effective from firmware version 4.7 SP6 and p0612.8 = 1.
- Alarm A07012 is output after the alarm threshold is exceeded.
- when commissioning a catalog motor for the first time, the threshold value is copied from p0605 to p5390.
The following applies for temperature model 3:
- after the alarm threshold is exceeded, alarm A07012 is output and a calculated delay time (t = p5371/p5381) is
started.
- if the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011
is output.
Dependency: Refer to: r0034, p0605, p0612, r0632, p5391
Refer to: F07011, A07012, A07014
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The hysteresis is 2 K.
Description: Sets the fault threshold for monitoring the motor temperature for motor temperature models 1 and 3.
Fault F07011 is output after the fault threshold is exceeded.
The stator winding temperature (r0632) is used to initiate the signal.
The following applies for temperature model 1 (I2t):
- only effective from firmware version 4.7 SP6 and p0612.8 = 1.
- when commissioning a catalog motor for the first time, the threshold value is copied from p0615 to p5391.
Dependency: Refer to: r0034, p0612, p0615, r0632, p5390
Refer to: F07011, A07014
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The hysteresis is 2 K.
Description: Displays the ambient temperature for motor temperature model 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p0613.
p5390[0...n] Mot_temp_mod 1/3 alarm threshold / A thresh
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Unit group: 21_1 Unit selection: p0505
Not for motor type: ASM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°C] 200.0 [°C] 110.0 [°C]
p5391[0...n] Mot_temp_mod 1/3 fault threshold / F thresh
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Unit group: 21_1 Unit selection: p0505
Not for motor type: ASM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°C] 200.0 [°C] 120.0 [°C]
r5397 Mot_temp_mod 3 ambient temperature image p0613 / AmbTmp image p0613
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8019
P-Group: Displays, signals Unit group: 21_1 Unit selection: p0505
Not for motor type: ASM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]