2 Parameters
2.2 List of parameters
Description: Connector output for interconnecting the PZD (setpoints) received via interface 2 in the word format.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
Dependency: Refer to: r8860, r8890, r8891, r8892, r8893
Notice: Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r8850 or r8860.
Note: IF2: Interface 2
PZD1 to PZD4 are displayed bit-serially in r8890 to r8893.
Description: Selects the PZD (actual values) to be sent via interface 2 in the word format.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
Note: IF2: Interface 2
r8850[0...3] CO: IF2 PZD receive word / IF2 PZD recv word
ENC Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 2485, 2491,
9204, 9206
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: 4000H Expert list: 1
Min Max Factory setting
- - -
p8851[0...24] CI: IF2 PZD send word / IF2 PZD send word
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Integer16 Dyn. index: - Func. diagram: 2493, 9210
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: 4000H Expert list: 1
Min Max Factory setting
- - 0