2 Parameters
2.2 List of parameters
Note: The interface configuration (p8900 and following) is activated with p8905 = 1.
The parameter is not influenced by setting the factory setting.
Description: Sets the DHCP mode for the Industrial Ethernet interface (X127) on the Control Unit.
The actual DHCP mode is displayed in parameter r8914.
Value: 0: DHCP off
2: DHCP on, identification using MAC address
3: DHCP on, identification via name of station
Dependency: Refer to: p8905, r8914
Note: The interface configuration (p8900 and following) is activated with p8905.
The parameter is not influenced by setting the factory setting.
Description: Setting to activate the interface configuration for the Industrial Ethernet interface (X127) on the Control Unit.
p8905 is automatically set to 0 at the end of an operation.
Value: 0: No function
1: Activate configuration
2: Activate and save configuration
3: Delete configuration
Dependency: Refer to: p8900, p8901, p8902, p8903, p8904
Refer to: A08561
Note: When a project is downloaded, the interface configuration is only activated if, in the offline project, parameter p8905
is set = 1 or 2.
For p8905 = 1:
The interface configuration (p8900 and following) is activated.
For p8905 = 2:
The interface configuration (p8900 and following) is activated and saved to non-volatile memory.
For p8905 = 3:
The interface configuration is reset to the factory setting at all points.
The factory settings for the interface configuration are loaded on activation (p8905 = 1) or at the next POWER ON.
Description: Activation of the FTP server.
Permits the FTP access to the /INSTALL/SINAMICS directory of the memory card.
Value: 0: No
1: Yes
p8904 IE DHCP mode / IE DHCP mode
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
p8905 IE Interface configuration / IE IF config
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
p8908 Activate FTP / Act FTP
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting