2 Parameters
2.2 List of parameters
SINAMICS G130/G150
880 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the IP address for the onboard PROFINET interface on the Control Unit.
The actual IP address is displayed in r8931.
Dependency: Refer to: p8925, r8931
Note: The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
Description: Sets the default gateway for the onboard PROFINET interface on the Control Unit.
The actual standard gateway is displayed in r8932.
Dependency: Refer to: p8925, r8932
Note: The setting p8922[0...3] = 0 or p8922 = p8921 (own IP address) means that a standard gateway has not been set.
The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
Description: Sets the subnet mask for the onboard PROFINET interface on the Control Unit.
The actual subnet mask is displayed in r8933.
Dependency: Refer to: p8925, r8933
Note: The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
Description: Sets the DHCP mode for the onboard PROFINET interface on the Control Unit.
The actual DHCP mode is displayed in r8934.
Value: 0: DHCP off
2: DHCP on, identification using MAC address
3: DHCP on, identification via name of station
p8921[0...3] PN IP address / PN IP addr
CU_G130_PN,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p8922[0...3] PN Def Gateway / PN Def Gateway
CU_G130_PN,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p8923[0...3] PN Subnet Mask / PN Subnet Mask
CU_G130_PN,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p8924 PN DHCP Mode / PN DHCP mode
CU_G130_PN,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0