SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
885
2 Parameters
2.2 List of parameters
Note: The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
Description: Sets the standard gateway for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Dependency: Refer to: p8945, r8952
Note: The setting p8942[0...3] = 0 or p8942 = p8941 (own IP address) means that a standard gateway has not been set.
The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
Description: Sets the subnet mask for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Dependency: Refer to: p8945, r8953
Note: The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
Description: Sets the DHCP mode for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Value: 0: DHCP off
2: DHCP on, identification using MAC address
3: DHCP on, identification via name of station
Dependency: Refer to: p8945, r8954
Notice: When the DHCP mode is active (p8944 not equal to 0), then PROFINET communication via this interface is no longer
possible! However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note: The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
p8942[0...3] CBE2x Default Gateway / CBE2x Def Gateway
CU_G130_PN (PN
CBE20),
CU_G150_PN (PN
CBE20),
CU_G130_DP (PN
CBE20),
CU_G150_DP (PN
CBE20)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p8943[0...3] CBE2x Subnet Mask / CBE2x Subnet Mask
CU_G130_PN (PN
CBE20),
CU_G150_PN (PN
CBE20),
CU_G130_DP (PN
CBE20),
CU_G150_DP (PN
CBE20)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p8944 CBE2x DHCP Mode / CBE2x DHCP Mode
CU_G130_PN (PN
CBE20),
CU_G150_PN (PN
CBE20),
CU_G130_DP (PN
CBE20),
CU_G150_DP (PN
CBE20)
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0