2 Parameters
2.2 List of parameters
SINAMICS G130/G150
904 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the upper limit for the function "Safely Limited Position" (SLP).
Index: [0] = Limit value SLP1 (SE1)
[1] = Limit value SLP2 (SE2)
Dependency: Refer to: p9501, p9535, p9562
Refer to: C01715
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The following applies to the setting of these limits:
- p9334[x] > p9335[x]
- p9334[x] must lie in the valid traversing range (-737280 ... 737280).
SLP: Safely Limited Position / SE: Safe software limit switches
Description: Sets the lower limit for the function "Safely Limited Position" (SLP).
Index: [0] = Limit value SLP1 (SE1)
[1] = Limit value SLP2 (SE2)
Dependency: Refer to: p9501, p9534, p9562
Refer to: C01715
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The following applies to the setting of these limits:
- p9334[x] > p9335[x]
- p9335[x] must lie in the valid traversing range (-737280 ... 737280).
SLP: Safely Limited Position / SE: Safe software limit switches
Description: Sets the lower limit for the function "Safely Limited Position" (SLP).
Index: [0] = Limit value SLP1 (SE1)
[1] = Limit value SLP2 (SE2)
Dependency: Refer to: p9501, p9534, p9562
Refer to: C01715
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The following applies to the setting of these limits:
- p9334[x] > p9335[x]
- p9335[x] must lie in the valid traversing range (-737280 ... 737280).
SLP: Safely Limited Position / SE: Safe software limit switches
p9334[0...1] SI Motion SLP upper limit values (Motor Module) / SI Mtn SLP uplimMM
VECTOR_G (Safety
rot)
Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2822
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-2147000.000 [°] 2147000.000 [°] 100000.000 [°]
p9335[0...1] SI Motion SLP lower limit values (Motor Module) / SI Mtn SLPlowLimMM
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2822
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-2147000.000 [mm] 2147000.000 [mm] -100000.000 [mm]
p9335[0...1] SI Motion SLP lower limit values (Motor Module) / SI Mtn SLPlowLimMM
VECTOR_G (Safety
rot)
Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2822
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-2147000.000 [°] 2147000.000 [°] -100000.000 [°]