SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
91
2 Parameters
2.2 List of parameters
Description: Sets the number of Power unit Data Sets (PDS).
The value corresponds to the number of power units connected together for a parallel circuit configuration.
Dependency: Refer to: p0107, r0107
Note: This parameter is only significant for drive objects A_INFEED and VECTOR with a parallel circuit configuration.
Description: The power unit data set is assigned to a power unit using this parameter.
This unique component number is assigned when parameterizing the topology.
Only component numbers can be entered into this parameter that correspond to a power unit.
Dependency: Refer to: p0107, r0107
Note: For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Detection of the main components of the drive object selected via the index.
Description: Detects the power unit assigned to this drive and data set.
Note: While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate power unit.
For parallel circuit configurations, the parameter index is assigned to a power unit.
p0120 Number of Power unit Data Sets (PDS) / PDS count
VECTOR_G, B_INF Can be changed: C1(3) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Data sets Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 8 1
p0121[0...n] Power unit component number / PU comp_no
VECTOR_G, B_INF Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Data sets Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0
p0124[0...n] Main component detection using LED / M_comp detect LED
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0124[0...n] Power unit detection via LED / PU detection LED
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0