2 Parameters
2.2 List of parameters
SINAMICS G130/G150
98 List Manual (LH2), 07/2016, A5E03263479A
Description: This parameter is used to assign the data set to a DRIVE-CLiQ Hub Module.
This unique component number is assigned when parameterizing the topology.
Only the numbers of components operated as hubs can be entered in these parameters.
[0] = DRIVE-CLiQ node 1
[1] = DRIVE-CLiQ node 2
Description: Detects the Terminal Module assigned to this drive and data set.
Note: While p0154 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Terminal Module.
Description: Detects any DRIVE-CLiQ Hub Module that has been assigned.
Description: Setting to activate/deactivate a Voltage Sensing Module (VSM).
Value: 0: Deactivate component
1: Activate component
2: Component deactivate and not present
Recommendation: After inserting a component, before activating, first wait for Alarm A01317.
Dependency: Refer to: r0156
Refer to: A01314, A01317
p0151[0...1] DRIVE-CLiQ Hub Module component number / Hub comp_no
HUB Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Data sets Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0
p0154 Terminal Module detection via LED / TM detection LED
TM31, TM120, TM150,
TM54F_MA,
TM54F_SL
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0154 DRIVE-CLiQ Hub Module detection via LED / Hub detection LED
HUB Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0155[0...n] Voltage Sensing Module activate/deactivate / VSM act/deact
VECTOR_G Can be changed: C1(4), T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: p0150 Func. diagram: -
P-Group: Data sets Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1