existing boards. The power requirements of the connected terminals (determined by means of Figure
3-13) are then added to this figure.
Battery current drain of the terminals
Figure 3-13 Hicom 150 E OfficePro - battery current drain of terminals
Formula for calculating battery power requirements
The bridging time is determined on the basis of Figure 3-12.
The cabinet with the greatest load determines the overall system bridging time when
calculations are made in relation to a multi-cabinet system.
Any external loads (e.g. NT 1) that are fed by the USVI must be accessed at 0.04 A per watt
of the consumer.
Table 3-9 Hicom 150 E OfficePro -
board power requirements
Board Power
requirements
CBMOD -Q2960- 0.80 A
SLA16 -Q2702- 0.10 A
SLMC8 -Q2911- 0.10 A
SLMO24 -Q2901- 0.08 A