Operating
7.3 Relays
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
103
Screen
Note
Before activating this preset,
Sensor Mode (2.1.3.) (Page 163) must be set to Dual-Point
Difference, and
Span (2.2.2.) (Page 169) for Level 3 must be set.
Differential control of a screen or rake:
Parameter
Relay #
1
2
3
4
5
6
Level Source
(2.8.1.2.) (Page 194)
Difference or
average
Transducer
1
Transducer
2
Difference
or average
OFF OFF
Relay Function
(2.8.1.4.) (Page 195)
Fixed Duty Assist Level (H) Level (L) Level (H) -- --
ON Setpoint (2.8.1.5.)
(Page 197)
80% 90% 10% 90% -- --
OFF Setpoint
(2.8.1.6.) (Page 197)
20% 85% 15% 10% -- --
Alarms
General alarms at four setpoints:
Parameter
Relay #
1
2
3
4
5
6
Relay Function
(2.8.1.4.) (Page 195)
Level (H) Level (L) Level (HH) Level (LL) OFF OFF
ON Setpoint
(2.8.1.5.) (Page 197)
80% 20% 90% 10% -- --
OFF Setpoint
(2.8.1.6.) (Page 197)
75% 25% 85% 15% -- --