Operating
7.9 Pump control
HydroRanger 200 HMI
130 Operating Instructions, 06/2018, A5E36281317-AC
You can group pumps and use the same pumping algorithm separately on each group. If you
specify different pumping algorithms, then you do not need to use this parameter because
the pumps are already grouped by algorithm.
Group pumps only when four pumps are using the same algorithm, and you want to split
them into two groups.
Pumps 1 and 2 will operate as a group, and Pumps 3 and 4 will operate as another group.
Pump Group (2.8.2.2.)
1 *Group 1 (Page 201)
Groups Pumps 1 and 2
Pump Group (2.8.2.2.)
2 *Group 1 (Page 201)
Pump Group (2.8.2.2.)
3 Group 2 (Page 201)
Groups Pumps 3 and 4
Pump Group (2.8.2.2.)
4 Group 2 (Page 201)
A flush valve stirs up the sediment at the bottom of the well during pumping, so that it doesn’t
accumulate. These parameters will control any relays set with Relay Function (2.8.1.4.)
(Page 195) = Flush Valve. Most sets of parameters will work with only one or two changes;
however, for these parameters to work, all of them must be set to a value.
The flush valve connects to Relay 4 and the watched pump is on Relay 1.
Relay Selector (2.10.3.1.)
- 4 Flush valve is connected to Relay 4
Flush Pump (2.10.3.2.)
Global 1 Watch Relay 1 to count pump cycles
Flush Cycles (2.10.3.3.)
Global 3 Open the flush valve for 3 cycles
Flush Interval (2.10.3.4.)
Global 10 Use the flush value every 10 cycles
Flush Duration (2.10.3.5.)
Global 120 Open the flush valve for 120 seconds