Relay controlled by communications
A relay can be controlled directly by a remote system through communications. No other
control schemes can then be used with a relay configured this way. Communications can be
used to force status of some control relays, such as pumps.
Relay Function (2.8.1.4.)
5 Communication Sets Relay 5 to communications con-
You can find out how much an individual pump has been used by viewing the pump records
parameters.
Current RUN time Pump Run Time (3.2.9.3.) (Page 260)
Pump Hours (3.2.9.2.) (Page 260)
Pump Starts (3.2.9.4.) (Page 260)
Total pump RUN on occurrences
Pump Run-ONs (3.2.9.5.) (Page 260)
Rakes or screens are mounted on the inflow channel of the wastewater treatment plant to
prevent debris from clogging the equipment. When material builds up on the screen, a level
differential is created, and the water level is higher in front of the screen than behind it. When
this differential reaches the programmed setpoint, the device activates a relay to operate
mechanical rakes that clean the screen and ensure a steady flow.