7.12 Open Channel Monitoring (OCM)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
151
7.12.5
Universal calculation support
When the Primary Measuring Device (PMD) doesn’t fit one of the standard types, it can be
programmed using a universal characterization. When Primary Measuring Device (2.13.2.)
(Page 240) = Universal, then the head/flow breakpoints must be entered into Universal Head
vs. Flow (2.13.6.) (Page 247)
Two curve types are supported:
Universal Linear Flow Calculation (Page 240) (piece wise linear)
Universal Curved Flow Calculation (Page 240) (cubic spline)
Both are shown in the following chart.
7.12.6
Typical flow characterization
Flow
Curved
Linear
Head
Characterization is achieved by entering Head 1 (2.13.6.1.1.) (Page 247) and its
corresponding Flow 1 (2.13.6.1.2.) (Page 248), either from empirical measurement or from
the manufacturer's specification.
Increasing the number of defined breakpoints will increase the accuracy of the flow
measurement.
Breakpoints should be concentrated in areas exhibiting the higher degrees of nonlinear
flow. A maximum of 32 breakpoints can be defined.
For Universal Linear Flow Calculation, Maximum Head and Maximum Flow must be
entered as breakpoints.
For Universal Curved Flow Calculation, values in Maximum Head (2.13.4.2.), Maximum
Flow (2.13.4.3.) are automatically used.