Parameter reference
8.5 Quick Start Wizards
HydroRanger 200 HMI
162 Operating Instructions, 06/2018, A5E36281317-AC
8.5
Quick Start Wizards
Wizards group together all the settings needed for a particular feature, for easy
configuration. The device offers several Wizards. All can be accessed via the local push
buttons.
For more details on the Wizards listed below, see Quick Start Wizards (Page 59).
Quick Start (1.1.) (Page 61)
Quick Start Level (1.1.1.)
(Page 61)
Quick Start Volume (1.1.2.) (Page 66)
Quick Start Flow (1.1.3.) (Page 73)
Pump control (1.2.) (Page 83)
8.6
Setup (2.)
8.6.1
Sensor (2.1.)
8.6.1.1
Units (2.1.1.)
Determines sensor measurement units used when Sensor Mode (2.1.3.) (Page 163) is set to
Level, Space, Distance, or Head.
Options
*M (meters)
CM (centimeters)
MM (millimeters)
FT (feet)
IN (inches)
8.6.1.2
Level selector (2.1.2.)
Sets the Level Point index for all parameters applicable to this sub-menu.
Options
*Level 1
Level 2
Level 3