Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
170 Operating Instructions, 06/2018, A5E36281317-AC
8.6.2.4
Empty (2.2.4.)
Enters distance, in Units (2.1.1.) (Page 162), from the face of the transducer to the process
empty point.
Index
Transducer
Values
Range: 0.000 ... 99.000 m [or equivalent, depending on Units (2.1.1.) (Page 162)
]
Preset: 5.000 m [or equivalent, depending on Units (2.1.1. (Page 162)) ]
Alters
Span (2.2.2.) (Page 169)
Altered by
Units (2.1.1.) (Page 162)
Related
Blanking (2.2.6.) (Page 171)
Level (3.2.8.3.) (Page 256)
Distance % (3.2.8.4.) (Page 256)
Setting this value also sets Span (2.2.2.) (Page 169), unless Span was already set to
another value. For distance operation [Sensor Mode (2.1.3) (Page 163) = Distance], Span is
preset to Empty.
Empty
Span