Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
173
Fill rate/minute (2.3.2.)
Adjusts the device’s response to increases in the actual material level [or advance to a
higher Material Level (2.4.5.) (Page 178)].
Range: 0.000 ... 99.00 m [or equivalent, depending on Units (2.1.1.) (Page 162)]
Preset: 20% of Span (2.2.2.)
Response Rate (2.3.4.) (Page 174)
• Units (2.1.1.) (Page 162)
• Span (2.2.2.) (Page 169)
• Material level (2.4.5.) (Page 178)
Enter a value slightly greater than the maximum vessel filling rate. This value, in Units
(2.1.1.) (Page 162) per minute, is automatically altered when Response Rate (2.3.4.)
(Page 174) is altered.
Response rate (2.3.4.) value
Empty rate/minute (2.3.3.)
Adjusts the device’s response to decreases in the actual material level [or advance to a
lower Material Level (2.4.5.) (Page 178)].
Range: 0.000 ... 99.00 m [or equivalent, depending on Units (2.1.1.) (Page 162)]
Response Rate (2.3.4.) (Page 174)
• Units (2.1.1.) (Page 162)
• Span (2.2.2.) (Page 169)
• Material level (2.4.5.) (Page 178)
Enter a value slightly greater than the maximum vessel emptying rate. This value, in Units
(2.1.1.) (Page 162) per minute, is automatically altered when Response Rate (2.3.4.)
(Page 174) is altered.
Response rate (2.3.4.) value