Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
176 Operating Instructions, 06/2018, A5E36281317-AC
Sets the Level Point index for all parameters applicable to this sub-menu.
Filling indicator (2.3.9.)
The fill rate required to activate the LCD Filling indicator
Range: 0.000 ... 99.00 m [or equivalent, depending on Units (2.1.1.) (Page 162)]
Response Rate (2.3.4.) (Page 174)
• Units (2.1.1.) (Page 162)
• Span (2.2.2.) (Page 169)
• Empty rate/minute (2.3.3.) (Page 173)
This value [in Units (2.1.1.) (Page 162) per minute] is automatically set to 1/10 of the Fill
Rate/minute (2.3.2.) (Page 173).
Emptying indicator (2.3.10.)
The empty rate required to activate the LCD emptying indicator
Range: 0.000 ... 99.00 m [or equivalent, depending on Units (2.1.1.) (Page 162)]
Response Rate (2.3.4.) (Page 174)
• Units (2.1.1.) (Page 162)
• Span (2.2.2.) (Page 169)
• Empty rate/minute (2.3.3.) (Page 173)
This value [in Units (2.1.1.) (Page 162) per minute] is automatically set to 1/10 of the Empty
Rate/minute (2.3.3.) (Page 173).