Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
180 Operating Instructions, 06/2018, A5E36281317-AC
8.6.4.9
mA Fail-safe value (2.4.9.)
Sets the mA value to be reported when the fail-safe timer expires.
Note
Fail
-safe mode (2.4.4.) (Page 178) must be set to
Value
in order for the
Material Level
value
to be reported.
Index
mA Output
Values
Range: 0 ... 22 mA
Preset: 3.58 mA
8.6.5
Current Output (2.5.)
Sets the parameters applicable to the current value of the mA output.
8.6.5.1
mA output selector (2.5.1.)
Sets the mA output index for all parameter settings.
Options
*mA Output 1
mA Output 2
8.6.5.2
mA output range (2.5.2.)
Determines the mA output range.
Index
mA Output
Options
OFF
0 ... 20 mA
*4 ... 20 mA
20 ... 0 mA
20 ... 4 mA
Related
Milliamp output (2.5.9.) (Page 182)
If either 0 to 20 mA or 4 to 20 mA is selected, the mA output is directly proportional to the mA
Function. If either 20 to 0 mA or 20 to 4 mA is selected, then the output is inversely
proportional. After setting mA output range (2.5.2.), verify that Minimum mA limit (2.5.7.)
(Page 182) has a valid entry, as it is not changed automatically by setting the mA output
range (2.5.2.).