Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
183
Use for fail-safe operation, independent of the Material Level (2.4.5.) (Page 178).
mA output responds to Material Level (2.4.5.) (Page 178)
HI Produce the
mA output immediately.
Produce the Empty mA output immediately.
Last known value is held until normal operation resumes.
Value mA output goes to user-selected value defined in mA Fail-
safe Value (2.4.9.) (Page 180).
Current output function (2.5.3.) (Page 181)
4 mA output trim (2.5.11.)
Calibrates the 4 mA output
20 mA output trim (2.5.12.) (Page 183)
Adjust this value so the device indicates 4.00 mA when 4 mA Output Trim (2.5.11.) is
accessed.
1. Go to Milliamp Output (2.5.9.) (Page 182) and enter 4.00 mA.
2. Read the value indicated on the current meter or other connected device, and enter it in
mA output trim (2.5.11.)
The new
will be shown in the current meter or other connected device.
20 mA output trim (2.5.12.)
Calibrates the 20 mA output
4 mA Output Trim (2.5.11.) (Page 183)
Adjust this value so the device indicates 20.00 mA when 20 mA output trim (2.5.12.) is
accessed
Trimming the 20 mA value:
1. Go to Milliamp Output (2.5.9.) (Page 182) and enter 20.00 mA.
2. Read the value indicated on the current meter or other connected device, and enter it in
mA output trim (2.5.12.)
The new
will be shown in the current meter or other connected device.