Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
190 Operating Instructions, 06/2018, A5E36281317-AC
Allows for the Volume to be specified based on segments, if the tank shape is too complex
for any of the preconfigured shapes.
Enter up to 32 Level and Volume breakpoints (where Volume is known), if Vessel Shape
(2.7.2.) (Page 186) is set to Universal Linear or Universal Curved.
Each segment defined by the Level breakpoints (example: Level 1) requires a Volume
(example: Volume 1) for the level-to-volume calculations.
5