Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
194 Operating Instructions, 06/2018, A5E36281317-AC
Level source (2.8.1.2.)
Sets the level source for the indexed relay.
Index
Relays
Options
*Transducer 1
Transducer 2
Difference or Average
Altered by
Response rate (2.3.4.) (Page 174)
Fill rate/minute (2.3.2.) (Page 173)
Empty rate/minute (2.3.3.) (Page 173)
LOE timer (2.4.2.) (Page 177)
Material level (2.4.5.) (Page 178)
Preset applications (2.8.1.3.)
Selects the preset options to configure or bench test the unit.
Index
Global
Options
*OFF
Wet well 1
Wet well 2
Reservoir 1
Reservoir 2
Screen
Alarms
Alters
Level source (2.8.1.2.) (Page 194)
Relay function (2.8.1.4.) (Page 195)
ON setpoint (2.8.1.5.) (Page 197)
OFF setpoint (2.8.1.6.) (Page 197)
Pump by rate (2.8.1.8.) (Page 198)
Related
Sensor mode (2.1.3.) (Page 163)
Note
For detailed descriptions of the various preset applications, see Preset applications
(Page 100).
Before selecting a Preset Application, a Level, Volume or Flow Quick Start Wizard must
first be completed.
Select an application that is similar to yours and change the parameters required. If nothing
suits your application, refer to Relay function (2.8.1.4.) (Page 195).