Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
201
Relay selector (2.8.2.1.)
Sets the relay index for all parameters applicable to this sub-menu.
Organizes pumps into groups, for multiple pump rotations on one transducer.
Relay
Group 2
Relay Function (2.8.1.4.) (Page 195), when Relay Function (2.8.1.4.) (Page 195)
= Alternate Duty Assist or Alternate Duty Backup
Note
All relay ON/OFF points must be referenced fr
om Empty (2.2.4.) (Page 170) (bottom of the
Sensor Mode (2.1.3.) (Page 163) selection.
Relay fail-safe (2.8.2.3.)
Sets how individual relays react to a fail-safe condition, to allow for more flexible
programming.
Options
Response governed by Material level (2.4.5.) (Page 178)
Last known relay state retention.
To have the relay energize immediately on fail-safe.
To have the relay de-energize immediately on fail-safe.
Material level (2.4.5.) (Page 178)
Related
• LOE timer (2.4.2.) (Page 177)
• Relay function (2.8.1.4.) (Page 195)
Use this for operations independent of the Material Level (2.4.5.) (Page 178).