EasyManua.ls Logo

Siemens HydroRanger 200 HMI - Page 206

Siemens HydroRanger 200 HMI
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
204 Operating Instructions, 06/2018, A5E36281317-AC
Wall Cling Reduction (2.8.2.6.)
Transducer selector (2.8.2.6.1.)
Sets the transducer index for all parameters applicable to this sub-menu.
Level setpoint variation (2.8.2.6.2.)
Varies the ON and OFF setpoints to reduce material buildup on the walls [defined in Units
(2.1.1.) (Page 162)].
Values
Range: 0.000 ... 99999.000
Default: 0.000
Random setpoint range
Level setpoint ON
Level setpoint variation
Level setpoint OFF
This value is the range in which the setpoints are allowed to deviate. The pump ON and OFF
Setpoint values are randomly varied inside the range to ensure that the material level does
not consistently stop at the same point.
Advanced pump control modifiers
The following parameters from Pump Run-ON (2.8.2.7.) (Page 205) to Power Resumption
Delay (2.8.2.8.2.) (Page 207) affect only the relays set to Pump Control in Relay Function
(2.8.1.4.) (Page 195). See the Pump row in the Control column for details.

Table of Contents

Related product manuals