Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
211
8.6.10.3
Multiplier (2.10.1.2.)
Use this feature if the remote totalizer (the device connected to the relay set to Relay
Function (2.8.1.4.) (Page 195) = Totalizer) updates too slowly or rapidly.
Index
Single-point model
Dual-point model
Global
Transducer
Options
0.001
0.01
0.1
*1
10
100
1,000
10,000
100,000
1,000,000
10,000,000
Related
Sensor mode (2.1.3.) (Page 163)
Relay function (2.8.1.4.) (Page 195)
Relay interval setpoint (2.8.2.4.) (Page 202)
Relay duration (2.10.1.3.) (Page 211)
This parameter is relevant only if Operation is set to OCM or Pumped Volume [Sensor Mode
(2.1.3.) (Page 163) = Flow rate in open channel or Pump Totalizer].
The relays on the device have a maximum frequency of 2.5 Hz. Enter the factor (powers of
10 only) by which actual volume is divided, prior to Remote Totalizer count increment.
Example: For a Remote Totalizer update by 1000s of volume units, enter 3.
8.6.10.4
Relay duration (2.10.1.3.)
Use this feature (if desired) to adjust the minimum contact closure duration of a relay set as
a totalizer or flow sampler [Relay Function (2.8.1.4.) (Page 195) = Totalizer or Flow
Sampler].
Index
Global
Values
Range: 0.1 ... 1024 seconds
Preset: 0.188 seconds
Related
Relay function (2.8.1.4.) (Page 195)
Enter minimum contact closure duration (in seconds) required by the device connected.