Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
226 Operating Instructions, 06/2018, A5E36281317-AC
Short shot floor (2.11.2.11.)
Enter the minimum echo strength, in dB above 1 uV, derived from a short shot to be
considered for evaluation.
Range: 0 ... 100
• Number of short shots (2.1.11.) (Page 166)
• Short shot frequency (2.1.7.) (Page 165)
• Long shot duration (2.1.10.) (Page 166)
• Short shot bias (2.11.2.10.) (Page 225)
• Short shot range (2.11.2.12.) (Page 226)
Short shot range (2.11.2.12.)
Enter the maximum distance in Units (2.1.1.) (Page 162) to be measured using short shot
echoes.
Range: 0 ... 10 m or equivalent, depending on Units (2.1.1.) (Page 162)
Transducer (2.1.5.) (Page 164)
• Number of short shots (2.1.11.) (Page 166)
• Short shot frequency (2.1.7.) (Page 165)
• Long shot duration (2.1.10.) (Page 166)
• Short shot bias (2.11.2.10.) (Page 225)
• Short shot floor (2.11.2.11.) (Page 226)
• Short Shot Range (2.11.2.12.)
This feature is automatically altered when Transducer (2.1.5.) (Page 164) is altered.