Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
226 Operating Instructions, 06/2018, A5E36281317-AC
Short shot floor (2.11.2.11.)
Enter the minimum echo strength, in dB above 1 uV, derived from a short shot to be
considered for evaluation.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: 0 ... 100
Preset: 50
Related
Number of short shots (2.1.11.) (Page 166)
Short shot frequency (2.1.7.) (Page 165)
Long shot duration (2.1.10.) (Page 166)
Short shot bias (2.11.2.10.) (Page 225)
Short shot range (2.11.2.12.) (Page 226)
Short shot range (2.11.2.12.)
Enter the maximum distance in Units (2.1.1.) (Page 162) to be measured using short shot
echoes.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: 0 ... 10 m or equivalent, depending on Units (2.1.1.) (Page 162)
Preset: 1.000
Altered by
Transducer (2.1.5.) (Page 164)
Related
Number of short shots (2.1.11.) (Page 166)
Short shot frequency (2.1.7.) (Page 165)
Long shot duration (2.1.10.) (Page 166)
Short shot bias (2.11.2.10.) (Page 225)
Short shot floor (2.11.2.11.) (Page 226)
Short Shot Range (2.11.2.12.)
This feature is automatically altered when Transducer (2.1.5.) (Page 164) is altered.