Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
240 Operating Instructions, 06/2018, A5E36281317-AC
8.6.13.2
Primary measuring device (2.13.2.)
The type of primary measuring device (PMD) used.
Index
Single-point model
Dual-point model
Global
Transducer
Options
* OFF (no calculation)
Exponential devices [see Flow Exponent (2.13.4.1.) (Page 241)]
Palmer-Bowlus Flume [see PMD Dimensions (2.13.5.) (Page 246)]
H-Flume [see PMD Dimensions (2.13.5.) (Page 246)]
Universal Linear Flow Calculation [see Head 1 (Page 247) and Flow 1 (Page 248)]
Universal Curved Flow Calculation [see Head 1 (Page 247) and Flow 1 (Page 248)]
Rectangular Flume BS-3680 [see PMD Dimensions (2.13.5.) (Page 246)]
Thin Plate V-Notch Weir BS-3680 [see PMD Dimensions (2.13.5.) (Page 246)]
Alters
Flow Exponent (2.13.4.1.) (Page 241)
PMD Dimensions (2.13.5.) (Page 246)
Flowrate Units (2.13.4.7.) (Page 245)
Altered by
Sensor Mode (2.1.3.) (Page 163)
Related
Maximum Head (2.13.4.2.) (Page 243)
Maximum Flow (2.13.4.3.) (Page 243)
Zero Head (2.13.4.5.) (Page 244)
Head 1 (2.13.6.1.1.) (Page 247)
Flow 1 (2.13.6.1.2.) (Page 248)
The device is pre-programmed for common PMD flow calculations. If your PMD is not listed,
select the appropriate Universal Flow Calculation.
Associated parameters Maximum Head (2.13.4.2.) (Page 243), Maximum Flow (2.13.4.3.)
(Page 243), and Zero Head (2.13.4.5.) (Page 244) may be scroll accessed. If Sensor Mode
(2.1.3.) (Page 163
) = Flow rate in open channel, this value is preset to
1
. If Sensor Mode
(2.1.3.) (Page 163
) is not set for
OCM
, it is preset to
0
.
8.6.13.3
Auto zero head (2.13.3.)
Calibrates Zero Head (2.13.4.5.) (Page 244) based on actual head measurements.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: -999 ... 9999
Altered by
Response rate (2.3.4.) (Page 174)
Related
Empty (2.2.4.) (Page 170)
Offset reading (2.12.6.) (Page 238)
Zero head (2.13.4.5.) (Page 244)
Process temperature (2.11.1.3.) (Page 218)