Parameter reference
8.7 Maintenance and Diagnostics (3.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
257
Volume (3.2.8.5.)
Shows the calculated volume of material.
Index
Level
Values
Range: -999 ... 9999
Related
Maximum volume (2.7.3.) (Page 188)
Rate (3.2.8.6.)
Shows the rate of material level change in Units (2.1.1) (Page 162) per minute.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: -999 ... 9999 (Read only)
Altered by
Rate filter (2.3.5.) (Page 175)
Related
Units (2.1.1.) (Page 162)
Span (2.2.2.) (Page 169)
A negative rate indicates the vessel is emptying.
Volume rate (3.2.8.7.)
Shows the rate of change of volume in percent
of
maximum
volume
per minute.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: -999 ... 9999 (Read only)
Related
Inflow/discharge adjust (2.7.7.) (Page 189)
This value is used internally to calculate inflow in pumped volume applications
[Inflow/discharge Adjust (2.7.7.) (Page 189) = Based on Rate Estimation].
Reading maximum (3.2.8.8.)
Shows the highest reading calculated (in normal Reading units).
Index
Level
Values
Range: -999 ... 9999 (read only)
Related
Reading minimum (3.2.8.9.) (Page 258)
To reset the values once the installation is working correctly, enter the value
0.0
.