Parameter reference
8.7 Maintenance and Diagnostics (3.)
HydroRanger 200 HMI
264 Operating Instructions, 06/2018, A5E36281317-AC
Hardware status (3.2.12.1.)
Shows the results of ongoing hardware tests in the communications circuitry.
Index
Global
Values
*Pass
No errors
Fail Error occurred communicating with card; communications should
resume.
Err1 No module installed, or module not supported; SmartLinx commu-
nications have been disabled
Related
Hardware Status Code (3.2.12.2.) (Page 264)
Hardware Error Count (3.2.12.3.) (Page 264)
If
Fail
or
Err1
is displayed in Hardware Status (3.2.12.1.), go to Hardware Status Code
(3.2.12.2.) (Page 264) and Hardware Error Count (3.2.12.3.) (Page 264) for information
about the error.
Hardware status code (3.2.12.2.)
Indicates the precise cause of
Fail
or
Err1
condition from Hardware Status (3.2.12.1.)
(Page 264).
Index
Global
Value
*
No error
8
No SmartLinx card installed
Any other value Error code; provide this code to your Siemens representative for
troubleshooting
Related
Hardware Status (3.2.12.1.) (Page 264)
Hardware error count (3.2.12.3.)
Shows the count that increments by
1
each time
Fail
is reported in Hardware Status
(3.2.12.1.) (Page 264).
Index
Global
Values
Range: 0 ... 9999
Error count; provide this number to your Siemens representative for troubleshooting.
Related
Hardware Status (3.2.12.1.) (Page 264)