Parameter reference
8.8 Communication (4.)
HydroRanger 200 HMI
268 Operating Instructions, 06/2018, A5E36281317-AC
8.8.3
Communications timeout (4.3.)
Sets the maximum time allowed between receiving a request and transmitting the response.
Index
Communications Port
Options
Range: 0 ... 60 000 milliseconds
Preset: 5 000 milliseconds
If the maximum time is exceeded, no response will be transmitted, and the action required
may not be completed.
8.8.4
Protocol (4.4.)
Sets the communications protocol used between the device and other devices.
Index
Communications Port
Options
Communications Port disabled
Dolphin protocol
Modbus ASCII slave serial
*Modbus RTU slave serial
The device supports the internationally recognized Modbus standard in both ASCII and RTU
formats. Other protocols are available with optional SmartLinx cards.
8.8.5
Serial baud rate (4.5.)
Sets the communication rate with the master device.
Index
Communications Port
Options
4.8 kbaud
9.6 kbaud
*19.2 kbaud (preset for Port 2)
*115.2 kbaud (preset for Port 1)
This specifies the rate of communication in kbaud. Any value may be entered but only the
values shown above are supported. The baud rate should reflect the speed of the connected
hardware and protocol used.