Technical data
11.2 Operating conditions
HydroRanger 200 HMI
296 Operating Instructions, 06/2018, A5E36281317-AC
11.2
Operating conditions
Location Indoor/outdoor
Altitude
2 000 m max.
Ambient temperature -20 ... 50 °C (-5 ... 122 °F)
Relative humidity
Wall Mount: suitable for outdoors (Type 4X /
NEMA 4X, IP65 Enclosure)
Panel Mount: suitable for outdoors (Type 3 /
NEMA 3, IP54 Enclosure)
Installation category
II
Pollution degree
4
11.3
Performance
Accuracy
1
0.25 % of maximum range or 6 mm (0.24 inch),
whichever is greater.
Resolution
1
0.1 % of program range
2
or 2 mm (0.08 inch),
whichever is greater.
Memory
2 MB static RAM
1 MB flash EPROM
Range 0.3 m (1 ft) to 15 m (50 ft), dependent on trans-
ducer
Temperature compensation
Range: -50 to 150 °C (-58 to 302 °F)
Source Integral transducer sensor
TS-3 temperature sensor
Programmable fixed temperature
1
Measurement performance under reference operating conditions and configuration.
2
Program range is defined as the empty distance from the face of the transducer [Empty
(2.2.4.) (Page 170)] plus any range extension [Range Extension (2.2.7.) (Page 172)].