Installing/mounting
4.2 Mounting Instructions
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
29
4.2
Mounting Instructions
4.2.1
Mounting locations
Recommended
Ambient temperature is always within -20 to +50 °C (-4 to +122 °F)
Device display window is at shoulder level, unless most interaction is through a SCADA
system
Local display buttons are easily accessible
Cable length requirements are minimized
Mounting surface is free from vibration
Sufficient room to swing device lid open
Avoid
Exposure to direct sunlight. (Provide a sun shield to avoid direct sunlight.)
Proximity to high voltage/current runs, contactors, SCR or variable frequency motor
speed controllers
Note
Recommended maximum torque for lid screws must not exceed 0.9 Nm (8 in
-lbs).
4.2.2
Mounting on wall
Note
When routing cable through a conduit, please follow the instructions in
routing cable through
a conduit
(Page 32).