Communications
C.6 Modbus
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
323
The Modbus protocol is supported in the base unit and can be configured using the
Communication (4.) (Page 267) parameters.
To set up communications with a Modbus RTU master device on Port 2 using RS-485, set
the following parameters:
Protocol (4.4.) (Page 268) 2 *Modbus RTU slave serial
Device Address (4.2.) (Page 268) 2 1
Serial Baud Rate (4.5.) (Page 269)
Data Bits (4.7.) (Page 269)
Stop Bits (4.8.) (Page 270)
Modem Available (4.9.) (Page 268)
Parameter Index Location (4.11.) (Page 268)
Other protocols are available through optional SmartLinx communications modules. Details
on how to install and program these modules are contained in the SmartLinx documentation.