5.9 mA output
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
45
5.9
mA output
For more information, consult parameter Current Output (2.5.) (Page 180).
Note
The device CANNOT be synchronized with the following products: MultiRanger Plus,
HydroRanger Plus, OCM
III.
5.10
Level system synchronization
When using multiple ultrasonic level monitors, running the transducer cables in separate
grounded metal conduits is recommended.
When separate conduits are not possible, synchronize the level monitors so that no unit
transmits while another is waiting for echo reception.
Synchronizing with another MultiRanger 200 HMI/HydroRanger 200 HMI, or other Siemens
instruments (DPL+, SPL, XPL+, LU01, LU02, LU10, LUC500, MultiRanger 100/200,
HydroRanger 200, EnviroRanger, MiniRanger, SITRANS LUT400):
Mount the level monitors together in one cabinet.
Use a common power (mains) supply and ground (earth) for all units.
Interconnect the SYNC terminals of all level monitors
Set parameter Shot synchro (2.1.13.) (Page 167)
For assistance, contact your Siemens representative, or go to
www.siemens.com/processinstrumentation