5.11 Power
HydroRanger 200 HMI
46 Operating Instructions, 06/2018, A5E36281317-AC
5.11
Power
Note
Before applying power to the device for the first time, ensure any con
nected alarm/control
equipment is disabled until satisfactory system operation and performance is verified.
Notes for AC power connections:
[AC-Powered Units] All current-carrying conductors must be protected by a fuse or circuit
breaker in the building installation, having a breaking capacity of up to 15A.
[AC-Powered Units] A circuit breaker or switch in the building installation, marked as the
disconnect switch, must be in close proximity to the equipment and within easy reach of
the operator, and must disconnect all current-carrying conductors.
Ensure that the device is connected to a reliable ground.
5.12
Digital communication
Wiring the device for communications allows it to be integrated into a full SCADA system or
an industrial LAN. The device can also be directly connected to a computer running
SIMATIC PDM.