Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
68 Operating Instructions, 06/2018, A5E36281317-AC
Selects the source of the temperature reading used to adjust the speed of sound.
Transducer
Fixed Temperature
For more information, see Temperature source (2.11.1.4.) (Page 219).
Sets the temperature of the source when there is no temperature-sensing device connected.
This parameter only displays if Fixed Temperature is selected for Temperature Source.
Range: -100.0 ... +150.0 °C
Defines the vessel shape and allows the device to calculate
instead of
. If
is selected, no volume conversion is performed. Select the vessel shape matching the
monitored vessel or reservoir.
For illustrations, see Vessel shape (2.7.2.) (Page 186). If Universal Linear or Universal
Curved is selected, enter values for level and volume breakpoints after completing the
wizard Table 1-8 (2.7.8.) (Page 190).
A vessel shape must be selected to proceed through the Quick Start Volume Wizard.