EasyManua.ls Logo

Siemens HydroRanger 200 HMI - Page 70

Siemens HydroRanger 200 HMI
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
68 Operating Instructions, 06/2018, A5E36281317-AC
Temperature source
Selects the source of the temperature reading used to adjust the speed of sound.
Index
Transducer
Options
*AUTO
Fixed Temperature
Transducer
External TS-3
Average of Sensors
For more information, see Temperature source (2.11.1.4.) (Page 219).
Fixed Temperature
Sets the temperature of the source when there is no temperature-sensing device connected.
This parameter only displays if Fixed Temperature is selected for Temperature Source.
Value
Range: -100.0 ... +150.0 °C
Default: +20.0 °C
Vessel shape
Defines the vessel shape and allows the device to calculate
Volume
instead of
Level
. If
None
is selected, no volume conversion is performed. Select the vessel shape matching the
monitored vessel or reservoir.
Options
None
Flat Level Bottom
Conical Bottom
Parabolic Bottom
Half Sphere Bottom
Flat Sloped Bottom
Flat Ends
Parabolic Ends
Sphere
Universal Linear
Universal Curved
For illustrations, see Vessel shape (2.7.2.) (Page 186). If Universal Linear or Universal
Curved is selected, enter values for level and volume breakpoints after completing the
wizard Table 1-8 (2.7.8.) (Page 190).
A vessel shape must be selected to proceed through the Quick Start Volume Wizard.

Table of Contents

Related product manuals