Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
75
Selects the source of the temperature reading used to adjust the speed of sound.
Transducer
Fixed Temperature
For more information, see Temperature source (2.11.1.4.) (Page 219).
Sets the temperature of the source when there is no temperature-sensing device connected.
This parameter only displays if Fixed Temperature is selected for Temperature Source.
Range: -100.0 ... +150.0 °C
Sensor measurement units
Note
For the purpose of this example, all values are assum
ed to be in meters.
Sets the distance from the face of the transducer to the process empty point
Level
Range: 0.000 ... 99.000 m
Preset: 5.000 m