Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
85
Pump hours
Sets the amount of time that pump relay has run, defined in hours.
Index
Relay
Values
Range: 0 ... 999999
This parameter displays only if a Service Ratio algorithm is selected for Relay Function.
ON setpoint
Sets the process point at which the relay changes from its
Normal
state.
Index
Relay
Values
Range: -999 ... 9999
Preset: ----
For most applications, the relay is tripped at this point. This parameter is set according to
Span (2.2.2.) (Page 169), even when another reading, such as volume, is shown on the
LCD.
OFF setpoint
Sets the process point at which the relay returns to its
Normal
state.
Index
Relay
Values
Range: -999 ... 9999
Preset: ----
For most applications, the relay is reset at this point. This parameter is set to Span (2.2.2.)
(Page 169), even when another reading, such as volume, is shown on the LCD.