Commissioning
6.6 Requesting an echo profile
HydroRanger 200 HMI
86 Operating Instructions, 06/2018, A5E36281317-AC
Configure another relay
Gives option to configure more relays or end the wizard.
Options
YES Returns to the Relay Function menu
NO
Completes the QS Pump Control configuration
End of QS Volume Wizard
Note
For QS to be successful, all changes must be applied.
Options
BACK, CANCEL, FINISH
Display returns to 1.1 Quick Start menu when Quick Start is successfully com-
pleted or cancelled. If CANCEL is selected, no changes are written to the device.
To transfer Quick Start values to the device and return to PROGRAM menu, press
DOWN
arrow
(Finish). Then press
LEFT
arrow three times to return to Measurement mode.
6.6
Requesting an echo profile
1. In PROGRAM mode, navigate to:
Main Menu > Diagnostics (3.2.) > Echo Profile (3.2.2.).
2. Press
RIGHT
arrow to request a profile.
Confidence
1
Algorithm BLF (best of first or largest echo)
2
Distance from transducer to target
Echo
TVT
3. Use
UP
or
DOWN
arrow to scroll to an icon. When an icon is highlighted, that
feature becomes active.
4. To move a cursor, press
RIGHT
arrow to increase the value,
LEFT
arrow to
decrease.