Operating
7.2 Dual-point models
HydroRanger 200 HMI
92 Operating Instructions, 06/2018, A5E36281317-AC
For differential or average operation with a single-point device, set Operation to Sensor
Mode (2.1.3.) (Page 163) = Dual-Point Difference (differential) (Page 163) or Dual-Point
Average (average) (Page 163) and connect two transducers of the same type. All of the
relevant parameters then become indexed by the correct transducer:
Indexed by Transducer 1 or 2
3
Indexed by
measurement
1 = Transducer 1
2 = Transducer 2
3 = Calculated Level (average or difference)
The device starts in an OFF state and does not take Level measurements. For measurement
setup, configure these basic parameters:
If the application uses two Level Points, provide the basic information for each point
separately.
Sensor mode (2.1.3.)
(Page 163)
Material (2.1.6.)
(Page 165)
Material = *Liquid
Response rate (2.3.4.)
(Page 174)
Max. Process Speed = *Medium (1.0 m/min)
Max. Process Speed = Fast (10.0 m/ min)
Transducer (2.1.5.)
(Page 164)
Transducer = XPS-10 (single-point preset)
Units (2.1.1.)
Global Meters Units = Meters
Empty (2.2.4.)
(Page 170)
Span (2.2.2.)
(Page 169)