EasyManua.ls Logo

Siemens LGA41.153A27 - Technical Specifications; General Unit Data; Environmental Conditions

Siemens LGA41.153A27
15 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8/15
Building Technologies Division CC1N7418en
21.06.2016
Technical data
Mains voltage
- Only with LGA63...
A
C 220 V 15 %...AC 240 V +10 %
A
C 100 V –15 %...AC 110 V +10 %
A
C 230 ±10 %
Mains frequency 50...60 Hz ±6 %
Power consumption 3 VA
Perm. mounting position Optional
Degree of protection IP40 (when integrated)
Safety class I (burner control with plug-in base)
Input current at terminal 1 Max. 5 A
Permissible cable lengths
Detector cable, laid separately
Max. 3 m with 100 pF/m line capacitance
Perm. electrical rating
- Terminal 4 Max. 4 A
- Terminal 5 Max. 1 A
- Terminal 6 Max. 2 A
- Terminal 7 Max. 2 A
- Terminal 8 Max. 4 A
- Terminal 9 Max. 0,1 A
- Terminal 10 Max. 1 A
Cable length terminal 20 m at 100 pF/m
Weight
A
pprox. 180 g
Storage
DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+60 °C
Humidity <95 % r.h.
Transport
DIN EN 60721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -50...+60 °C
Humidity <95 % r.h.
Operation
DIN EN 60721-3-3
Climatic conditions Class 3K5
Mechanical conditions Class 3M2
Temperature range 0...+60 °C
For LGA41.173A27 and LGA52.171B27:
-20...+60 °C
Humidity <95 % r.h.
Installation altitude Max. 2,000 m above sea level
Caution!
Condensation, formation of ice and ingress of water are not permitted!
If this is not observed, there is a risk of loss of safety functions and a risk of
electric shock.
General unit data
Environmental
conditions

Other manuals for Siemens LGA41.153A27