In principle, whenever lockout occurs, the fuel supply will immediately be shut down. If
that takes place between startup and preignition, which is not indicated by a symbol,
the usual cause is air pressure switch «LP» shutting down, or a premature, faulty flame
signal.
• After a mains failure or in the event of un-
dervoltage:
New startup with full program sequence
on power restoration
• Premature flame signal from the start of «t1»:
Immediate lockout
• Contacts of air pressure switch «LP» have
welded during «tw»:
Prevention of startup
• No air pressure signal:
Lockout on completion of «t10»
• Air pressure failure on completion of «t10»:
Immediate lockout
• Burner does not ignite:
Lockout on completion of «TSA»
• Flame is lost during operation:
Immediate lockout
After lockout, the LGB... will remain locked (lockout cannot be changed).
This state will also be maintained in the event of mains voltage failure.
Whenever lockout occurs, the burner control can immediately be reset.
Lockout and control sequence indication
The position of the programming mechanism can be seen through the viewing window
on the front of the unit. In the event of fault, the programming mechanism stops and
thus the lockout indicator also. The symbol in the viewing window indicates both the
position in the control sequence and the type of fault according to the following legend:
No startup since the start control loop is open
IIII
Interval «tw» or «t10» (LGB21...)
Interval «tw» or «t11» (LGB22... / LGB32...)
Interval «tw», «t3» or «TSA» (LGB41...)
Air damper fully open (LGB22... / LGB32...)
P
Lockout due to absence of air pressure signal
ÍÍÍ
Interval «t1», «t3» and «TSA» (LGB21...)
Interval «t1», «t3» («t12») (LGB22... / LGB32...)
Release of fuel
1
Lockout since there is no flame signal on completion of the first safety time
2
Release of second fuel valve (LGB21... / LGB41...)
Release of load controller (LGB22... / LGB32...)
3
Lockout since there is no flame signal on completion of the second safety time
(LGB41...)
zzzz
Partial load or nominal load operation (or return to the operating position)
Control sequence in
the event of fault
Lockout
Resetting the LGB...