Building Technologies Basic Documentation LMV27... CC1P7541en
26 Parameter level 17.12.2018
Wait until the burner is operating and symbol
or is no longer highlighted!
The startup sequence stops in phase 36 Traveling to ignition position.
The ignition position can be adjusted under cold conditions.
F
or
A
and
or
P
Vh
mi n
s%
Bild 118/0707
Ignition position P0 can only be set after symbol
or is no longer highlighted.
For fuel, keep
F
depressed, for air
A
.
Press
or to adjust the value.
When symbol
or is no longer
highlighted, the next curvepoint P1 can be
selected with
.
P
Vh
mi n
s%
Bild 117/0707
Phase Traveling to ignition position
P
Vh
mi n
s%
Bild 119/0707
Phase Preignition
P
Vh
mi n
s%
Bild 120/0707
Phase 1st safety time (ignition transformer ON)
P
Vh
mi n
s%
Bild 121/0707
Phase 1st safety time (ignition transformer OFF),
preignition time OFF
P
Vh
mi n
s%
Bild 122/0707
Phase Interval 1