EasyManua.ls Logo

Siemens LMV27.100x2 - Page 172

Siemens LMV27.100x2
219 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
172/219
Building Technologies Basic Documentation LMV27... CC1P7541en
26 Parameter level 17.12.2018
F
and
A
and
or
P
Vhsmin%
Bild 139/0807
Press
or to change the value as
required.
Example: 00.0
F
or
A
P
Vhmins%
Bild 140/0707
Release
F
or
A
.
The required value will be adopted.
Example: P5:50.0:46.0
>3 s
P
Vh
mi n
s%
Bild 124/0707
Keep
depressed for >3 s.
CALC appears.
P
Vhmins%
7´Bild 141/0707
The display jumps to P6.
All curvepoints from P5 to P9 have now been
automatically recalculated (linear interpolation):
Curvepoint Value 1
fuel
Value 2
air
P5
50.0 46.0
P6
57.5 57.0
P7
65.0 68.0
P8
72.0 79.0
P9
80.0 90.0
>3 s
P
Vh
mi n
s%
Bild 124/0707
Keep
depressed for >3 s.
CALC appears.
P
Vhmins%
Bild 142/0707
The display jumps to P4.
All curvepoints from P1 to P5 have now been
automatically recalculated (linear interpolation):
Curvepoint Value 1
fuel
Value 2
air
P5
50.0 46.0
P4
45.5 40.0
P3
41.0 35.0
P2
36.5 29.5
P1
32.0 24.0