178/219
Building Technologies Basic Documentation LMV27... CC1P7541en
26 Parameter level 17.12.2018
To the next curvepoint
Back to the previous
curvepoint.
A
and
or
P
Vh
mi n
s%
Bild 153/0707
Curvepoint P2 can only be adjusted when
symbol
or is no longer highlighted.
Fuel valve V2 will be switched on.
Keep
depressed.
Press
or to adjust the value.
When symbol
or is no longer
highlighted, the next curvepoint P2of can be
selected with
.
Back to the previous
curvepoint.
P
Vh
mi n
s%
Bild 154/0707
Curvepoint P2of is now adjusted.
The LMV27 remains at P2.
Adjust the switch-off point with no travel.
Now, the curvepoint is approached
dynamically when traveling from P2 to P1.
When symbol
or is no longer
highlighted, the next curvepoint P1 can be
selected with
.
To the next curvepoint
Back to the previous
curvepoint.
P
Vh
mi n
s%
Bild 155/0707
Automatic mode will be released when, after
reaching P1, the curve settings are quit with
ESC.
If the settings are aborted earlier (ESC or
shutdown due to fault), start prevention OFF
UPr is still active until all curvepoints are set.
ES
P
Vhmins%
Bild 94/0707
When symbol or is no longer
highlighted, ESC can be pressed a second
time.