Building Technologies Basic Documentation LMV27... CC1P7541en
27 Parameter list 17.12.2018
Par. Parameter
Number of
Type Edit Value range Increment Default Password level
no.
elements
Min. Max. setting Write Read
272
Oil: Interval 2
1 Time Edit 0,4 s 60 min 0,2 s 2 s HF HF
273
Oil: Afterburn time
1 Time Edit 0,2 s 60 s 0,2 s 8 s HF HF
274
Oil: Postpurge time
1 Time Edit 0,2 s 108 min 0,2 s 0,2 s HF HF
276 Oil: Input pressure switch-min
1 = active from phase 38
2 = active from safety time
1 Selection Edit 1 2 1 1 HF HF
277 Oil: Input pressure switch-max/POC
1 = pressure switch-max
2 = POC
3 = not used
4 = not used
1 Selection Edit 1 4 1 1 HF HF
280 Repetition limit value loss of flame
1 = no repetition
2 = 1 repetition
Recharging time:
After the
Operation phase 1
1 Std_u8 Edit 1 2 1 2 OEM OEM
Note!
Parameters 280 and 240 refer to the same value.
This means that no separate setting is possible for oil /
gas or fuel 0 / fuel 1.
281 Oil: Point in time oil is ignited
0 = short preignition (phase 38)
1 = long preignition (with fan) (phase 22)
1 Selection Edit 0 1 1 1 HF HF
284 Oil: Postpurge time (abortion with load controller-ON 1 Time Edit 1 s 108 min 0,2 s 1 s HF HF
288 Oil: Prepurge time (OEM) 1 Time Edit 5 s 60 min 0,2 s 15 s OEM HF
400
Ratio control curves
401
Ratio control curve fuel actuator (only curve settings)
13 Std_s16 Edit 90° 0,1° 0°; 0°; 15°;
undefined
HF HF
402
Ratio control curve air actuator (only curve settings)
13 Std_s16 Edit 90° 0,1° 0°; 90°; 45°;
undefined
HF HF
500
Ratio control
501
No-flame positions fuel actuator
Index 0 = home position
3 Std_s16 Edit 90° 0,1° Index
0
Value
HF HF