Building Technologies Basic Documentation LMV27... CC1P7541en
27 Parameter list 17.12.2018
Par. Parameter
Number of
Type Edit Value range Increment Default Password level
no.
elements
Min. Max. setting Write Read
Index 1 = prepurge position
Index 2 = postpurge position
1
2
15°
502
No-flame positions air actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
3 Std_s16 Edit 90° 0,1° Index
0
1
2
Value
90°
45°
HF HF
544 Ramp modulating 1 Std_u8 Edit 32 s 80 s 1 s 32 s HF HF
545
Lower output limit
undefined = 20 %
1 Output Edit / clear 20% 100% 0,1% undefined HF HF (GA)
546
Upper output limit
undefined = 100 %
1 Output Edit / clear 20% 100% 0,1% undefined HF HF (GA)
600
Actuators
601 Selection of reference point
Index 0 = fuel
Index 1 = air
Setting values:
0 = CLOSED (<0°)
1 = OPEN (>90°)
2 Selection Edit 0 1 1 Index
0
1
Value
1
0
OEM HF
602
Actuator's direction of rotation
Index 0 = fuel
Index 1 = air
Setting values:
0 = counterclockwise
1 = clockwise (exclusively for SQM3)
2 Selection Edit
0 1 1 Index
0
1
Value
0
0
OEM HF
606
Tolerance limit of position monitoring [0.1°]
Index 0 = fuel
Index 1 = air
Greatest position error where a fault is securely detected
error detection band: (parameter 606-0.6°) to parameter 606
2 Std_u8 edit 0,5° 0,1° Index
0
1
Value
1,7°
1,7°
OEM HF
611 Type of reference
Index 0 = fuel
Index 1 = air
2 Std_u8 Edit 0 3 1 Index
0
1
Value
0
0
OEM HF